. VI (Vacuum Interrupter)

Production range
for Circuit Breaker :
7.2kV to 145kV
630A to 3150A − 20kA to 50kA
for Switch and Contactor :
7.2kV to 36kV
400A, 630A-3kA/4kA
Features
simplified arc quenching method
simplified construction and high quality
no evacuation tube
compact body

For Circuit-Breakers

Rated voltage
Rated current
Short circuit breaking current with at least 30-40% DC component
and outlet diameter of vacuum interrupter (mm)
kV
A
12.5kA
16kA
20kA
25kA
31.5kA
40kA
50kA
12/15
630
M52QC
(Ø65)
M41QC
(Ø73)
800/1250
M51RC
(Ø82)
1600/2000
M61RQC
(Ø94)
M71SC
(Ø94)
M81SC
(Ø110)
2500/3150
M71TC
(Ø110)
M81TC
(Ø132)
MA131TC
(Ø150)
17.5/24
630
M52QC*
(Ø65)
800/1250
M102R
(Ø94)
1600/2000
M102S
(Ø94)
 
2500/3150
M132TC
(Ø120)
M203TCB
(Ø120)
36/38
630
M83QC*
(Ø65)
M93QC*
(Ø94)
800/1250
M163RC*
(Ø110)
1600/2000
M163SC
(Ø120)
 
2500/3150
M203TCB*
(Ø120)
M253TC*
(Ø132)
72.5
1250/2000
MA467SC*
(Ø150)
123
2000
M8301TX*
(Ø190)
145
2000
M10014TX*
(Ø240)

*:Applied for use in insulating gas
We can manufacture the VI to be applied into high-pressure insulating gas (dry-air etc.)

For Switches and Contactors

Rated voltage(kV) Rated breaking current(kA) Impulse withstand voltage(kV) Number of operation cycles at rated current Rated current(A)
400A 630A
12
4
45

2.5 X 105

Yes  
12
4
85
1 X 104 Yes Yes
24
4
150
1 X 104   Yes
36
3
200
1 X 104   Yes

Copyright 2003 Japan AE Power Systems Corporation. All rights reserved.